Driver LC 60W 150–550mA 230V o4a NFC h16 EXC4
NEW
16 mm excite NFC non-SELV series
Product description
- NEW: lumDATA (DALI-2 part ext. 251, 252 and 253)
- Dimmable built-in constant current LED driver
- Dimming range 1 to 100 %
- For luminaires of protection class I and protection class II
- Adjustable output current between 150 and 550 mA
- Max. output power 60 W
- Up to 94 % efficiency
- Power input on stand-by < 0.14 W
- Nominal lifetime up to 100,000 h
- 5 years guarantee
Housing properties
- Low profile metal casing with white cover
- Only 16 mm housing height
- Type of protection IP20
Interfaces
- Near field communication (NFC)
- one4all (DALI-2 DT 6, DSI, switchDIM, corridorFUNCTION)
- Terminal blocks: 0° push terminals
Functions
- Adjustable output current in 1-mA-steps (NFC, DALI)
- Fulfills DALI-2 parts: 251 (Luminaire data), 252 (Energy reporting) and 253 (Diagnostics & Maintenance)
- Constant light output function (eCLO)
- Power-up fading at AC
- Switch off the driver with fade2zero
- Protective features (overtemperature, short-circuit, overload, no-load)
- Suitable for emergency escape lighting systems acc. to EN 50172
Benefits
- Flexible configuration via companionSUITE
- Support NFC multiple programming (full carton box)
- Application-oriented operating window for maximum compatibility
- Best energy savings due to low stand-by losses and high efficiency
- Reliability proven by lifetime up to 100,000 h and 5 years guarantee
Typical applications
- For linear/area lighting in office applications
- Luminaire types:
-
-
-
- Approval marks:
-
-
-
-
-
-
-
-
-
-
-
-
Rated supply voltage |
220 – 240 V |
AC voltage range |
198 – 264 V |
DC voltage range |
176 – 280 V |
Mains frequency |
0 / 50 / 60 Hz |
Overvoltage protection |
320 V AC, 48 h |
Typ. rated current (at 230 V, 50 Hz, full load)
(1)
(2) |
288 mA |
Typ. current (220 V, 0 Hz, full load, 15 % dimming level)
(2) |
57 mA |
Leakage current (PE) |
< 500 µA |
Max. input power |
65 W |
Typ. efficiency (at 230 V, 50 Hz, full load)
(2) |
94 % |
λ (at 230 V, 50 Hz, full load)
(1) |
0.99 |
Typ. power consumption on stand-by
(3) |
< 0.14 W |
Typ. input current in no-load operation |
25.3 mA |
Typ. input power in no-load operation |
0.32 W |
In-rush current (peak / duration) |
31 A / 200 µs |
THD (at 230 V, 50 Hz, full load)
(1) |
< 5 % |
Starting time (AC mode) |
< 0.7 s |
Starting time (DC mode) |
< 0.35 s |
Switchover time (AC/DC)
(4) |
< 0.3 s |
Turn off time (at 230 V, 50 Hz, full load) |
< 50 ms |
Output current tolerance
(1) |
± 3 % |
Max. output current peak (non-repetitive) |
≤ output current + 40 % |
Output LF current ripple (< 120 Hz) |
± 1.5 % |
Output P_ST_LM (at full load) |
≤ 1 |
Output SVM (at full load) |
≤ 0.4 |
Max. output voltage (U-OUT) |
250 V |
Dimming range |
1 – 100 % |
Mains surge capability (between L - N) |
1 kV |
Mains surge capability (between L/N - PE) |
2 kV |
Surge voltage at output side (against PE) |
< 2 kV |
Type of protection |
IP20 |
Lifetime |
up to 100,000 h |
Guarantee |
5 Year(s) |
Dimensions L x W x H |
280 x 30 x 16 mm |
Type |
Output current
(1) |
Min. forward voltage |
Max. forward voltage |
Max. output power |
Typ. power consumption (at 230 V, 50 Hz, full load) |
Typ. current consumption (at 230 V, 50 Hz, full load) |
tc point max. |
Ambient temperature ta |
LC 60/150-550/230 o4a NF h16 EXC4
|
150 mA |
45 V |
230.0 V |
34.5 W |
37.7 W |
169 mA |
87 °C |
-20 ... +70 °C |
LC 60/150-550/230 o4a NF h16 EXC4
|
200 mA |
45 V |
230.0 V |
46.0 W |
50.2 W |
200 mA |
85 °C |
-20 ... +65 °C |
LC 60/150-550/230 o4a NF h16 EXC4
|
250 mA |
45 V |
230.0 V |
57.5 W |
61.1 W |
270 mA |
85 °C |
-20 ... +65 °C |
LC 60/150-550/230 o4a NF h16 EXC4
|
300 mA |
45 V |
200.0 V |
60.0 W |
64.2 W |
282 mA |
84 °C |
-20 ... +60 °C |
LC 60/150-550/230 o4a NF h16 EXC4
|
350 mA |
45 V |
171.4 V |
60.0 W |
64.2 W |
280 mA |
84 °C |
-20 ... +60 °C |
LC 60/150-550/230 o4a NF h16 EXC4
|
400 mA |
45 V |
150.0 V |
60.0 W |
65.0 W |
283 mA |
84 °C |
-20 ... +60 °C |
LC 60/150-550/230 o4a NF h16 EXC4
|
450 mA |
45 V |
133.3 V |
60.0 W |
64.8 W |
283 mA |
83 °C |
-20 ... +55 °C |
LC 60/150-550/230 o4a NF h16 EXC4
|
500 mA |
45 V |
120.0 V |
60.0 W |
64.8 W |
284 mA |
83 °C |
-20 ... +55 °C |
LC 60/150-550/230 o4a NF h16 EXC4
|
550 mA |
45 V |
109.1 V |
60.0 W |
65.4 W |
286 mA |
80 °C |
-20 ... +50 °C |
Type |
Article number |
Environmental Product Declaration (EPD) |
LC 60/150-550/230 o4a NF h16 EXC4
|
28003603
|